CSI SECTION 04222
ARCHITECTURAL CONCRETE MASONRY
This suggested guide specification has been developed using the current edition
of the Construction Specifications Institute (CSI) “Manual Practice”,
including the recommendations for the CSI 3 Part Section Format. Additionally,
the development concept and organizational arrangement of the American Institute
of Architects (AIA) MASTERSPEC Program have been recognized in the preparation
of this guide specification. Neither CSI nor AIA endorse the use of specific
manufacturers and products
ED NOTE: THIS SECTION COVERS INFORMATION SPECIFIC TO ARCHITECTURAL CONCRETE MASONRY
UNITS FOR EXTERIOR AND/OR INTERIOR WALLS AS SINGLE WYTHE AND/OR MULTI WYTHE SYSTEMS
USED FOR LOADBEARING AND/OR NON LOADBEARING WALLS AS INDICATED ON THE PLANS AND/OR
SCHEDULE OF FINISHES.
Contents:
PART 1 GENERAL
1.01 SUMMARY
1.02 REFERENCES
1.03 SUBMITTALS
1.04 QUALITY ASSURANCE
1.05 DELIVERY, STORAGE, AND HANDLING
PART 2 PRODUCTS
2.01 MANUFACTURES
2.02 RELATED MATERIALS
2.03 SOURCE QUALITY CONTROL
PART 3 EXECUTION
3.01 MANUFACTURER'S INSTRUCTIONS
3.02 EXAMINATION
3.03 PREPERATION
3.04 INSTALLATION
3.05 CLEANING AND PROTECTION |
| |
| PART 1 GENERAL |
1.01 SUMMARY
ED NOTE: REVISE BELOW TO SUIT PROJECT CONDITIONS.
A. Section j Includes: Adams Architectural Concrete Masonry Units. |
| |
1. Adams Profile Split Face Units (PSF).
2. Adams Profile Split Face Single Score Units (PSF-1).
3. Adams Profile Split Face Double Score Units (PSF-2)
4. Adams Profile Wide Split Rib Four Units (PWSR-4).
5. Adams Profile Split Rib Two Units (PSR-2).
6. Adams Profile Split Rib Four Units (PSR-4).
7. Adams Profile Split Rib Eight Units (PSR-8).
8. Adams Brickstone Units (BS).
9. Adams Shadow Stone Units (SS).
10. Adams Castle Rock Units (CR).
11. Adams Profile Smooth Face Units (PSMF).
12. Adams Profile Smooth Face Single Score Units (PSMF-1).
13. Adams Profile Split Face/Profile Smooth Face/Decro-Face Sill Units
14. Adams Ashlarstone Units (AS)
15. Adams Decro-Face Units (DF)
16. Adams Decro-Face Single Score Units (DF-1)
17. Adams Decro-Face Column Units (DF Column)
18. Adams Decro-Face Oversize Units (DF Oversize) |
| B. Related Sections: Refer to Division
4 Masonry, Division 5 Metals, and Division 7 Thermal
and Moisture Protection Sections for the following: |
| |
1. Section 0410 Mortar and Masonry Grout.
2. Section 04150 Masonry Accessories.
3. Section 04200 Unit Masonry.
4. Section 04500 Masonry Restoration and Cleaning.
5. Section 05500 Metal Fabrications: Placement of loose steel lintels.
6. Section 07150 Dampproofing.
7. Section 07180 Water Repellents.
8. Section 07200 Insulation
a. Vermiculite/Perlite Loose Fill Insulation.
b. KORFIL Block Insulation.
c. Integra Wall System Insulation.
9. Section 07600 Flashing and Sheet Metal.
10. Section 07900 Joint Sealers. |
| |
1.02 REFERENCES
A. American Society for Testing and Materials (ASTM): |
| |
1. ASTM C 90-94a Standard Specification for
Load-Bearing Concrete Masonry Units.
2. ASTM C 140-94 Standard Methods of Sampling and Testing Concrete Masonry Units. |
| B. Joint Effort of the American Concrete
Institute, the American Society of Civil Engineers, and
the Masonry Society. |
| |
1. Building Code Requirements for Masonry
Structures (ACI 530- 92/ASCE 6-92/TMS
402-92).
2. Specifications for Masonry Structures (ACI 530.1-92/ASCE 6- 92/TMS 602-92).
3. Commentary of Building Code Requirements for Masonry Structures (ACI 520-92/TMS
402-92).
4. Commentary on Specifications for Masonry Structures (ACI 530.1- 92/ASCE 6-92/TMS
602-92). |
| |
1.03 SUBMITTALS
A. General: Prepare, review, approve, and submit specified submittals in accordance
with Division1 Submittals Sections. Submit the following: |
| |
1. Product Data: Submit product data for
each type of product specified, including certification
that each type complies with specified requirements.
2. Samples: Submit verification samples for colors, textures.
3. Test Report: Submit test report form an independent testing agency indicating
compliance with ASTM C 90 for concrete masonry units. |
| |
1.04 QUALITY ASSURANCE
A. Mockup (Field Constructed): Install at project site a job mockup
using acceptable products and manufacturer approved installation methods. Obtain
Owner’s
and Architect's acceptance of finish color, texture and pattern, joint sizes,
and installation workmanship standard.
ED Note: Specify Below Mockup size And Substrate. |
| |
1. Mockup Size: 3’4” (5 courses
high) by 4’0” (3 block wide) is recommended
as the minimum size.
2. Maintenance: Maintain mockup during construction for workmanship comparison;
remove and legally dispose of mockup when no longer required.
3. Incorporation: Mockup may be incorporated into final construction upon Owner's
and Architect's approval. |
| B. Pre-Installation Conference: Convene
prior to commencing work of this section, under provisions
of Section 01040 Coordination and Project Meetings. |
| |
|
|
1.05 DELIVERY, STORAGE, AND HANDLING
A. Ordering: Comply with manufacturer's ordering
instructions and lead time requirements to avoid construction
delays.
B. Storage and Protection: Store materials protected from exposure to harmful
weather conditions. |
| |
| PART 2 PRODUCTS |
ED NOTE: COORDINATE BELOW ARTICLE
WITH DIVISION 1 MATERIAL AND EQUIPMENT (PRODUCT OPTIONS
ANS SUBSTITUTIONS) SECTION, AND BIDDING DOCUMENTS, IF ANY.
2.01 MANUFACTURES
A. Acceptable Manufacturers; Adams Products Company, Oldcastle, Architectural
Products Group Companies. |
| |
1. Address: 5701 McCrimmon Parkway,
P.O. Box 189, Morrisville, NC 27560
Telephone 800-672-3131;
919-461-8210; Fax: 919-469-0509
2. Proprietary Product(s)/System(s):
Adams Architectural Concrete Masonry Units with integral water repellent agent.
Dry-Block producer complies with qualification criteria and is annually certified
by W..R. Grace & Company. |
| |
|
a. Size: Width (W) X Height (H) X Length (L).
b. Color: |
| |
|
1. A400M/A500M Series integral color with grey cement
(requires grey mortar,
pigment and tan sand).
2. A700M Series integral color with grey cement chips (requires grey mortar,
pigment and tan sand).
3. A800M Series integral color with white cement (requires white cement, pigment
and white sand).
4. Multicolor Series integral color with grey cement (requires grey mortar, pigment
and tan sand). |
| |
|
c. Minimum Net Area Average Compressive Strength: High
Strength Unit. Average of three units 3000PSI, individual
unit 2700 PSI. Exceeds ASTM C 90 standard average of three
units 1900 PSI, individual unit 1700 PSI.
d. Maximum Absorption: Low Absorption unit. The unit shall contain specific amounts
of the integral water repellent compound so the absorption is less than (7.5%)
and/or 10 lbs/CF. Exceeds ASTM C 90 standard of 13 lbs/CF absorption rate.
e. Weight Classification: High Density Unit. Normal Weight not less than 125
lbs/CF.
f. Exposes Face Finish:
|
| |
|
1. Adams Profile Split Face Units (PSF).
2. Adams Profile Split Face Single Score Units (PSF-1).
3. Adams Profile Split Face Double Score Units (PSF-2).
4. Adams Profile Wide Split Rib Four Units (PWSR).
5. Adams Profile Split Rib Two Units (PSR-2).
6. Adams Profile Split Rib Four Units (PSR-4).
7. Adams Profile Split Rib Eight Units (PSR-8).
8. Adams Brickstone Units (BS).
9. Adams Shadow Stone Units (SS).
10. Adams Castle Rock Units (CR).
11. Adams Profile Smooth Face units (PSMF).
12. Adams Profile Smooth Face Single Score Units (PSMF-1).
13. Adams Profile Split Face/Profile Smooth Face/Decro FaceSill Units.
14. Adams Ashlarstone Units (AS).
15. Adams Decro-Face Units (DF).
16. Adams Decro-Face Single Score Units (DF-1).
17. Adams Decro-Face Column Units (DF Column).
18. Adams Decro-Face Oversize Units (DF Oversize). |
| |
|
3. Product(s)/System(s)/Testing:
a. Architectural Unit
Product Standard: |
| |
|
1. Comply with ASTM C 90 for concrete masonry units.
2. Comply with Carolina Concrete Masonry Association (CCNMA) Architectural Concrete
Masonry Guideline Specification |
| |
|
|
2.02 RELATED MATERIALS
A. Mortar and Grout: Refer to Division 4 Masonry
Section for mortar and
grout
materials. |
| |
|
|
2.03 SOURCE QUALITY CONTROL
A. General: |
| |
1. Obtain Architectural Concrete Masonry
Units from a single source to ensure color, finish and
texture continuity.
2. Manufacturer shall not have less than ten (10) years experience for this type
of unit. |
| |
|
|
| PART 3 EXECUTION |
3.01 MANUFACTURER'S INSTRUCTIONS
A. Compliance: Comply with manufacturer's product data,
including product technical bulletins and product catalog
installation instructions. |
| |
|
|
3.02 EXAMINATION
A. Site Verification of Conditions: Verify substrate
conditions (which have been previously installed under
other sections) are acceptable for product installation
in accordance with accordance with manufacturer's instructions. |
| |
|
|
3.03 PREPARATION
A. Adjacent Surface Protection: Protect adjacent
work areas and finish surfaces
from damage during product installation. |
| |
|
|
3.04 INSTALLATION
A. General: Refer to Division 4 Masonry Section
for installation requirements.
B. Pattern: Install Architectural Concrete Masonry Units in pattern indicated
on drawings. Maintain pattern lines. Match approved job mockup.
C. Elevation Tolerances: Elevations of installed Architectural Concrete Masonry
units do not exceed 1/4” in 10’ or 3/8” in a story height of
20’ maximum, except for external corners, expansion joints and other conspicuous
lines, do not exceed 1/4” in any one story or 20’ maximum.
D. Expansion and Control Joints: Refer to Division 4 Unit Masonry section for
expansion and control joints. |
| |
|
|
3.05 CLEANING AND PROTECTION
A. Cleaning: |
| |
1. Good workmanship and job housekeeping
practices shall be used to minimize the need for cleaning
the masonry. Masonry wall should be dry brushed at end
of each days work and also after final pointing and should
be left clean and free from mortar droppings. Protect the
base of the wall from mud splashes and mortar droppings,
protect the wall by setting scaffolds so that mortar is
not deflected onto the wall and at the end of each day
set the scaffolding boards so that they do not deflect
rainfall onto newly laid masonry. The masonry laying technique
shall be such that mortar does not run down the face of
the wall, or smear the masonry face, after the joints are
tooled, cut off mortar tailings with the trowel and brush
excess mortar burrs and dust from the face of the masonry.
2. If after using the above outlined techniques, additional cleaning of masonry
is necessary, the technique, solutions and test area shall be approved by the
owner, architect and manufacturer in writing. The masonry shall be thoroughly
saturated prior to and at the time the cleaning solution is applied. Clean the
masonry only with an approved cleaning solution (Water, Vana Trol or Sure Klean
600) with a brush starting at the top of the masonry. The solutions and the method
of scraping shall be as outlined on the container by the manufacturer. Immediately
after cleaning a small area, the masonry shall be rinsed thoroughly with quantities
of water sufficient to rinse cleaning solution completely. High pressure water
and sandblasting shall not be used for cleaning except with the recommendation
of the manufacturer and the written approval of the architect and the owner.
3. Remove temporary coverings and protection of adjacent work areas. Repair or
replace damaged installed products. Remove construction debris from protected
site and legally dispose of debris. |
| B. Protection: Protect installed
product's finish surfaces from damage during construction. |
| |
|
| ED NOTE: IF NON PROPRIETARY SPECIFICATION
IS REQUIRED, DELETE ANY REFERENCE TO ADAMS PRODUCTS COMPANY.
THE REMAINING SPECIFICATION WILL BE A PERFORMANCE SPECIFICATION. |
| |
|
|
 |